Abstract

Nonselectivity and reserve areas of outgoing cables, distribution points, and transformer substations are determined in this article, as exemplified by city 6(10) kV cable network schemes with various short-circuit currents. An algorithm of fault finding which reduces personnel residence time in electrically hazardous areas is introduced. Temperature conditions of insulation are assessed using a model designed in ANSYS according to the relay protection and automation setting selection procedure.

Keywords: cable, insulation, relay protection, labour conditions, thermal analysis.